GE 85 PSX PMSX EAS

GE 85 PSX PMSX EAS
  • PERKINS water cooled diesel engine - 1500 rpm
  • Electronic governor
  • EP6 engine protection
  • GE 85 PSX – STAMFORD three-phase synchronous alternator
  • GE 85 PMSX – MARELLI three-phase synchronous alternator
  • Four pole circuit breaker
  • Super silenced
  • Bunded base
  • Trailer (option)
  • Ready for connection to automatic transfer unit
  • Meets EC directives for safety and noise level

 

Standard equipment

  • Diesel engine
  • Water Cooling
  • Battery 12V
  • Fuel level gauge
  • Engine protection
  • Electric starter
  • Low press. shut down
  • High water shut down
  • Over speed shut down
  • Battery charge alarm
  • Rpm meter
  • Hour meter
  • Battery voltmeter
  • Voltmeter
  • Frequency meter
  • Remote start
  • Synchronous alternator
  • Automatic voltage regulator
  • Circuit breaker
  • Terminal block
  • ammeter
  • Voltmeter phase selector
  • Emergency stop button
  • Siren
  • Ready for EAS/TCM
  • Central lifting eye
  • Cold start aid

 

Factory installation options

  • Electrical panel with sockets :1x400V 125A 3P+N+T CEE - 1x400V 63A 3P+N+T CEE - 1x400V 32A 3P+N+T CEE - 1x400V 16A 3P+N+T CEE - 2 x 230V 16A 2P+T CEE. The electrical panel requires an electrical protection : ELR-Earth Leakage Relay (GFI) or Isometer (Insulation monitors)
  • 50/60 Hz Selector
  • Earth Leakage Relay
  • Isometer (Insulation monitors)
  • Radio-control
  • Permanent Magnet Generator
  • Volt and Hz adjustable from control panel
  • Gauges – water temperature and oil pressure
  • Water heater WH
  • Automatic fuel transfer pump
  • Fuel tank 120l
  • Fuel tank 350l
  • 3-way valve fuel system with quick connection for external fuel tank supply

 

Options on request

  • 400V plug
  • 230V plug
  • Automatic transfer unit (AMF) EAS 111-805
  • Remote control TCM35
  • Earthing kit
  • Site tow CTL35
  • Adjustable site tow CTL115

 

Technical data

A.C. GENERATION - 50 Hz: Three-phase syncronous alternator, self-excited, self   regulated, brushless

*Stand-by three-phase power: 88 kVA (70.4 kW) / 400 V / 127 A

*P.R.P. three-phase power: 80 kVA (64 kW) / 400 V / 115 A

*P.R.P. single-phase power: 29 kVA / 230 V / 126 A

Cos φ: 0.8

Insulation class: H

*Output powers according to ISO 8528-1

ENGINE: 4-stroke diesel, turbocharged-air to air charge cooled , direct injection, water cooled

Model: PERKINS 1104C-44TAG1

*Stand-By net power: 78.4 kW (106.6 HP)

*P.R.P. net power: 71.3 kW (97 HP)

Cylinders/ Displacement: 4/ 4.4 l (4400 cm3)

Speed: 1500 rpm

Fuel consumption (75% of P.R.P.): 14.3 l/h

*Powers according to ISO 3046-1

GENERAL SPECIFICATIONS

Tank capacity: 230 l

Running time (75% of P.R.P.): 16 h       

IP protection degree: IP 44

*Dimensions LxWxH (mm): 2740x1200x1640

*Dry weight: 1655 k (GE 85 PSX EAS)

                     1620 kg (GE 85 PMSX EAS)

**Measured acoustic power LwA (pressure LpA): 95 dB(A) (70 dB(A) @ 7 m)

**Guaranteed acoustic power LwA (pressure LpA): 96 dB(A) (71 dB(A) @ 7 m)

*Dimensions and weight without trolley/trailer. **Acoustic power according to European Directive 2000/14/EC