Test

GE 455 FSX, FMSX EAS

GE 455 FSX, FMSX EAS
  • FPT (IVECO) water cooled diesel engine - 1500 rpm
  • Turbo aftercooled engine with electronic governor
  • Closed crankcase ventilation
  • EP6 engine protection
  • GE 455 FSX - STAMFORD three-phase synchronous alternator
  • GE 455 FMSX - MARELLI three-phase synchronous alternator
  • Four pole circuit breaker
  • Oil drain pump
  • Bunded Base
  • Two central lifting eyes
  • Meets EC directives for safety and noise level

 

Standard equipment

  • Diesel engine
  • Water Cooling
  • Battery 12V
  • Engine protection
  • Electric starter
  • Low press. shut down
  • High water shut down
  • Over speed shut down
  • Low fuel shut down
  • Battery charge alarm
  • Central lifting eye
  • Rpm meter
  • Hours meter
  • Battery voltmeter
  • Voltmeter
  • Frequency meter
  • Local/Remote start selector
  • Synchronous alternator
  • Automatic Voltage Regulator
  • Circuit breaker
  • Ammeter
  • Voltmeter phase selector
  • Emergency stop button
  • Siren
  • Ready for EAS/TCM
  • Fuel level gauge
  • Oil pressure gauge
  • Water temperature gauge

 

Factory installation options

  • Electrical panel with sockets :1x400V 125A 3P+N+T CEE - 1x400V 63A 3P+N+T CEE - 1x400V 32A 3P+N+T CEE - 1x400V 16A 3P+N+T CEE - 2 x 230V 16A 2P+T CEE. The electrical panel requires an electrical protection : ELR-Earth Leakage Relay (GFI) or Isometer (Insulation monitors)
  • ELR-Earth Leakage Relay (GFI)
  • Isometer (Insulation monitors)
  • Voltage regulation
  • Radio control
  • PMG (Permanent Magnet Generator)
  • Water heater WH
  • Low level water radiator sensor
  • Automatic fuel transfer pump
  • Fuel tank 120l
  • 3-way valve fuel system with quick connection for external fuel tank supply

 

Options on request

  • 400 plugs
  • 230 plugs
  • Automatic transfer unit (AMF) EAS 435 MTE-805
  • Earthing kit
  • Remote control TCM35

 

Technical data

A.C. GENERATION - 50 Hz: Three-phase synchronous alternator, self-excited, self-regulated, brushless

*Stand-by three-phase power: 440 kVA (352 kW) / 400 V / 635.1 A (GE 455 FSX)

                                                  450 kVA (360 kW) / 400 V / 649.5 A (GE 455 FMSX)

*P.R.P. three-phase power: 400 kVA (320 kW) / 400 V / 577.3 A (GE 455 FSX)

                                            410 kVA (328 kW) / 400 V / 591.8 A (GE 455 FMSX)

Cos φ: 0.8

Insulation class: H

*Output powers according to ISO 8528-1

ENGINE: 4-stroke diesel, turbocharged-air to air charge cooled, direct injection, water cooled

Model: FPT (IVECO) C13 TE3A

*Stand-By net power: 387 kW (526.3 HP))

*P.R.P. net power: 352 kW (478.7 HP)

Cylinders/ Displacement: 6 / 12.9 l (12900 cm3)

Speed: 1500 rpm

Fuel consumption (75% of P.R.P.): 68 l/h

*Powers according to ISO 3046-1

GENERAL SPECIFICATIONS

Tank capacity: 580 l

Running time (75% of P.R.P.): 8.5 h   

IP protection degree: IP 44

*Dimensions LxWxH (mm): 4100x1520x2150

*Dry weight: 4340 kg (GE 455 FSX)

                     4240 kg (GE 455 FMSX)

**Measured acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7 m)

**Guaranteed acoustic power LwA (pressure LpA): 98 dB(A) (73 dB(A) @ 7 m)

*Acoustic power according to European Directive 2000/14/EC