Test

GE 275 VPSX - VPMSX

GE 275 VPSX - VPMSX
  • VOLVO PENTA water cooled diesel engine - 1500 rpm
  • Common-rail engine with electronic governor
  • Control panel unit “GECO” with the following features :

   - automatic main failure (AMF) logic (EAS ONLY)

   - engine protection

   - Control of main electric and engine parameters

   - large lightback display – multilanguage messages

   - Back-up memory of the last 255 events

   - remote comunication via RS232 port

  • GE 275 VPSX – STAMFORD three-phase synchronous alternator
  • GE 275 VPMSX – MARELLI three-phase synchronous alternator
  • Four pole circuit breaker
  • Oil drain pump
  • Central lifting eye
  • Ready for connection to load transfer switch (ATS, ONLY EAS)
  • Meets EC directives for safety and noise level

 

Standard equipment

  • Diesel engine
  • Water Cooling
  • Battery 12V (2x12V)
  • Synchronous alternator
  • Automatic Voltage Regulator
  • Circuit breaker
  • Terminal block
  • Emergency stop button
  • Siren
  • Central lifting eye
  • Ready for PAC
  • GECO

Alarms: high water temperature – low oil pressure – low level water – overspeed – low level fuel – fail to start – battery charge damage low/ high battery voltage– unexpected stop - under/over generator frequency – under/over generator voltage – asymmetry generator voltage generator and main sequence phase error - maintance request.

Controls: water temperature gauge - oil pressure gauge - fuel level gauge - hours meter - rpm meter - number of start attempts - remaining time until maintance due. battery voltage – generator and main voltage: N-L1; N-L2; N-L3; L1-L2; L2-L3; L3-L1 – generator current: L1; L2; L3– generator and main frequency cos : L1, L2, L3, average – generator power: kVA, kW, kVAR L1, L2, L3, total – energy counter

 

Factory installation options

  • 50/60 Hz Selector
  • ELR-Earth Leakage Relay (GFI)
  • Volt and Hz adjustable from control panel
  • Permanent Magnet Generator
  • Water heater WH
  • Remote control by PC : via RS232 port (15m max.) - via RS485 port - via modem - via GSM modem - via GPRS - via Ethernet
  • Noise reduction baffles
  • Automatic fuel transfer pump
  • 3-way valve fuel system with quick connection
  • for external fuel tank feeding
  • Fuel tank 120
  • Foot container kit
  • Wheels container kit

 

Options on request

  • Load transfer switch PAC 300 MTE
  • Earthing kit

 

Technical data

A.C. GENERATION - 50 Hz: Three-phase synchronous alternator, self-excited, self-regulated, brushless

*Stand-by single-phase power: 275 kVA (220 kW) / 400 V / 397 A

*P.R.P. single-phase power: 250 kVA (200 kW) / 400 V / 261 A

Cos φ: 0.8

Insulation class: H

*Output powers according to ISO 8528-1

ENGINE: 4-stroke diesel, common-rail, turbocharged-air to air charge cooled , direct injection, water cooled

Model: VOLVO PENTA TAD734GE

*Stand-By net power: 241 kW (327 HP)

*P.R.P. net power: 216 kW (240 HP)

Cylinders/ Displacement: 6/ 7.15 l (7150 cm3)

Speed: 1500 rpm

Fuel consumption (75% of P.R.P.): 43.6 l/h

*Powers according to ISO 3046-1

GENERAL SPECIFICATIONS

Tank capacity: 250 l

Running time (75% of P.R.P.): 6 h      

IP protection degree: IP 44

*Dimensions LxWxH (mm) : 4000x1300x2000

*Dry weight: 3050 kg (GE 275 VPSX / GE 275 VPSX EAS)

                           3040 kg (GE 275 VPMSX / GE 275 VPMSX EAS)

**Measured acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7 m)

**Guaranteed acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7 m)

*Dimensions and weight without trolley/trailer. **Acoustic power according to European Directive 2000/14/EC