- FPT (IVECO) water cooled diesel engine - 1500 rpm
- Turbo aftercooled engine with electronic governor
- Closed crankcase ventilation
- EP6 engine protection
- GE 455 FSX - STAMFORD three-phase synchronous alternator
- GE 455 FMSX - MARELLI three-phase synchronous alternator
- Four pole circuit breaker
- Oil drain pump
- Bunded Base
- Two central lifting eyes
- Meets EC directives for safety and noise level
Standard equipment
- Diesel engine
- Water Cooling
- Battery 12V
- Engine protection
- Electric starter
- Low press. shut down
- High water shut down
- Over speed shut down
- Low fuel shut down
- Battery charge alarm
- Central lifting eye
- Rpm meter
- Hours meter
- Battery voltmeter
- Voltmeter
- Frequency meter
- Local/Remote start selector
- Synchronous alternator
- Automatic Voltage Regulator
- Circuit breaker
- Ammeter
- Voltmeter phase selector
- Emergency stop button
- Siren
- Ready for EAS/TCM
- Fuel level gauge
- Oil pressure gauge
- Water temperature gauge
Factory installation options
- Electrical panel with sockets :1x400V 125A 3P+N+T CEE - 1x400V 63A 3P+N+T CEE - 1x400V 32A 3P+N+T CEE - 1x400V 16A 3P+N+T CEE - 2 x 230V 16A 2P+T CEE. The electrical panel requires an electrical protection : ELR-Earth Leakage Relay (GFI) or Isometer (Insulation monitors)
- ELR-Earth Leakage Relay (GFI)
- Isometer (Insulation monitors)
- Voltage regulation
- Radio control
- PMG (Permanent Magnet Generator)
- Water heater WH
- Low level water radiator sensor
- Automatic fuel transfer pump
- Fuel tank 120l
- 3-way valve fuel system with quick connection for external fuel tank supply
Options on request
- 400 plugs
- 230 plugs
- Automatic transfer unit (AMF) EAS 435 MTE-805
- Earthing kit
- Remote control TCM35
Technical data
A.C. GENERATION - 50 Hz: Three-phase synchronous alternator, self-excited, self-regulated, brushless
*Stand-by three-phase power: 440 kVA (352 kW) / 400 V / 635.1 A (GE 455 FSX)
450 kVA (360 kW) / 400 V / 649.5 A (GE 455 FMSX)
*P.R.P. three-phase power: 400 kVA (320 kW) / 400 V / 577.3 A (GE 455 FSX)
410 kVA (328 kW) / 400 V / 591.8 A (GE 455 FMSX)
Cos φ: 0.8
Insulation class: H
*Output powers according to ISO 8528-1
ENGINE: 4-stroke diesel, turbocharged-air to air charge cooled, direct injection, water cooled
Model: FPT (IVECO) C13 TE3A
*Stand-By net power: 387 kW (526.3 HP))
*P.R.P. net power: 352 kW (478.7 HP)
Cylinders/ Displacement: 6 / 12.9 l (12900 cm3)
Speed: 1500 rpm
Fuel consumption (75% of P.R.P.): 68 l/h
*Powers according to ISO 3046-1
GENERAL SPECIFICATIONS
Tank capacity: 580 l
Running time (75% of P.R.P.): 8.5 h
IP protection degree: IP 44
*Dimensions LxWxH (mm): 4100x1520x2150
*Dry weight: 4340 kg (GE 455 FSX)
4240 kg (GE 455 FMSX)
**Measured acoustic power LwA (pressure LpA): 97 dB(A) (72 dB(A) @ 7 m)
**Guaranteed acoustic power LwA (pressure LpA): 98 dB(A) (73 dB(A) @ 7 m)
*Acoustic power according to European Directive 2000/14/EC