Product features

  • Automatic Controller capable of supporting:
    - Single Gas Panels
    - Single Gas Panels with supporting purge
    - Twin Gas panels (different source and destination)
    - Dual gas panels (same source and destination with auto changeover facility)
    - Supports MP3 and SBE3 configurations
  • Alarm and control unit for 5 external digital sensor inputs, 8 system analogue inputs and 6 system digital inputs
  • User adjustable purge cycles and  service mode set points
  • Line capacity calculator for optimised line purging
  • Exhaust failure switch fitted as standard
  • User selectable ACV (pn. operated cylinder valve)
  • Touchscreen Operation: All operation from ergonomically positioned Human Machine Interface
  • Industrial PLC controls all inputs and outputs as well as analogue signal processing
  • 2 potential free outputs (one each for warning or shutdown conditions)
  • Communication options: Ethernet, Profibus, Modbus RT and DeviceNet communications
  • Solenoid valves can be manually operated by user
    • An external junction box is supplied in order to allow fast connection of external sensors (e.g. gas detection) to the Flocontrol TS via a supplied 3 metre pre-plugged lead.
  • Optional Heating Control System Add-on box for cylinder jackets and panel heating
  • Digital inputs to be configured for NO or NC contacts
  • Plastic housing IP 65 for wall mounting
  • According to EC Directive 2004/108/EC (immunity and emission standard, measurement, control and laboratory use)
  • According to Low Voltage Directive 2006/95/EC
  • ATEX Equipment Directive 94/9/EC (Category 3 compliant where stated on the rating plate)
Technical data
Housing
Protection class:
Dimensions (WxHxD):
depending on cabinet

IP 54
635 x 220 x 200 mm
800 x 220 x 200 mm
 
Compatibility inputs
- mechanical switches
- 4-20 mA transducers
Digital inputs 
Power supply voltage:
Max. power:

24 V DC
15 mA (per channel)
Analogue inputs 
Max. voltage 
(open circuit):
Short circuit current:


24 V DC
25 mA
Output / pneumatic valves
Max. pressure:
Compatibility:


7 bar
inert gases
Power supply voltage
Max. power consumption
100-240V / 50-60Hz
2 A
Internal signals - LEDs 17 mm
- buzzer
NAMUR-Specification
Voltage:
Power input inactive:
Power input activated:

5 V DC - 25 V DC
IL < 1 mA
3 mA < IL < 15 mA